359

Low-voltage distribution cabinet -GGD series

2017-04-25

GGD cabinet: (ESS)

 

Electrical performance:

 

1) Basic electrical parameters

 

A) Rated insulation voltage: AC 660v (1000) v

 

GGD type low voltage distribution cabinet

 

B) Rated operating voltage: Main circuit: AC 380v (660V) auxiliary circuit: AC 380v (220v) DC 220v (110v)

 

C) Rated frequency: 50Hz

 

D) Rated current: ≤4000A

 

E) Rated peak withstand current (0.1s) 105KA

 

F) Rated short time withstand current (1s) 50KA

 

GCK series of low-voltage distribution cabinet is listed as a new type of energy-saving products, advanced control center structure, beautiful appearance, high electrical performance, high degree of protection, safe and reliable, easy maintenance, metallurgy, petroleum, chemical, electrical machinery, Spinning and other industries low-voltage power supply system ideal power distribution device.

 

Main technical performance

 

B) Rated operating voltage: 380V, 660V

 

C) Frequency of use: 50Hz

 

D) rated current: horizontal bus system 1600 ~ 3150A vertical bus system 400 ~ 800A

 

E) Rated short-time withstand current: horizontal bus 80KA rms / 1 second vertical bus 50KA rms / 1 second

 

F) Rated peak current: horizontal busbar 175KA vertical busbar 110KA

 

G) functional unit breaking capacity: 50KA

 

H) Peripheral protection class: IP40